AC5320Vrms / 5 seconds Between the Transformer jaws fitted parts and Case enclosure (except for jaws)
Conductor size
Approx. 32mm max.
Dimension
246(L) × 120(W) × 54(D)mm
Weight
Approx. 780g (including batteries)
Accessories
Battery R6P : 4pcs Instruction manual : 1pc 8304 (Resister for operation check : 1pc) 9128 (Hard case : 1pc)
•Crest factor < 3 (50Hz / 60Hz, peak value shall not exceed 60A) *4 counts or less are corrected to 0.
Why earth resistance can be found by only clamping it?
Rx, is defined as earth resistance under test, and R1, R2...Rn are defined as earth resistance of other measuring objects.
These earth resistances, R1, R2, Rn can be considered that they are connected in parallel. And they can be regarded as a combined resistance Rs. The Rs can be regarded small enough against Rx since a combined resistance consists of several resistances. Following is an equivalent circuit diagram of this circuit.
Voltage V is applied to the object (Resistance Rx) measured from the voltage injection transformer CT1, and the current I corresponding to the earth resistance is flowed. The current I is detected with detection transformer CT2, and object (Resistance Rx) measured can be put out by the calculation. (refer to the right diagram)