Language:
Currency:
VAT Mode:
Now In:
→ KEW 5406A RCD Tester
|
|
| • |
Custom microprocessor controlled for highest accuracy and reliability. |
| • |
3 LEDs for checking correct wiring status. |
| • |
0 and 180 degree phase angle switch permits quick tests and consistent readings. |
| • |
Digital read-out of tripping time. |
| • |
Constant current source circuitry ensures that a fluctuating mains voltage does not affect the accuracy of readings. |
| • |
Large custom digital display readout. |
| • |
Visual indication of reversed phase and neutral wiring at socket. |
| • |
Designed to IP54 Rating. |
| • |
Complies with IEC61557 |
| • |
Test of a large kind of RCD's: Standard, Selective, AC and A (DC sensitive breakers) | |
|
|
| |
| Rated Tripping Current |
|10/20/30/200/300/500mA |
| Fault Condition Settings |
|× 1/2, × 1, × 5, × DC, |AUTO RAMP |
| Trip Current Duration |
|1000ms, 200ms(×5) |
| Lowest Resolution |
|1ms |
| Trip Time Accuracy |
||±0.6%rdg±4dgt |
| Operating Voltage |
|230V+10%-15% |(195V~253V) 50Hz |
| Safety Standard |
|IEC61557-1,-6 |IEC61010-1 CAT.III 300V |IEC61010-2-031 Pollution Degree 2 |
| Withstand Voltage |
|3700V AC for 1 minute |
| IP Rating |
|IEC60529-IP54 |
| Dimensions |
|186(L) × 167(W) × 89(D)mm |
| Weight |
|800g approx. |
| Accessories |
|Molded plug test leads |Pouch for test leads |Shoulder Strap |Instruction Manual |
| Optional |
|7121(Distribution board test leads) | | |
| |
|
|
|
|
|
|
|
|
|