Language:
Currency:
VAT Mode:
Now In:
→ KEW 2412 20mA/200mA/2A/20A/200A/500A Leakage Clamp Meter
|
|
| • |
Digital clamp meter with tear drop shaped, medium size transformer jaws specially designed for leakage current measurement. |
| • |
Frequency filter switch to eliminate the effect of harmonics. |
| • |
Output terminal for connection to recorders and facility to operate from external power supply permit continuous leakage current monitoring. |
|
|
| |
AC A (50/60Hz) |
20/200mA/2/20/200/500A |±1.5%rdg±5dgt (20/200mA/2A) |±2%rdg±5dgt (20/200A) |±2.5%rdg±5dgt (500A) |
AC A (WIDE) |
20/200mA/2/20/200/500A |±1%rdg±3dgt [50/60Hz], |±5%rdg±5dgt [40~400Hz] (20/200mA/2A) |±1.5%rdg±3dgt [50/60Hz], |±5%rdg±5dgt [40~400Hz] (20/200A) |±2%rdg±3dgt [50/60Hz], |±5%rdg±5dgt [40~400Hz] (500A) |
| AC V |
600V |±2%rdg±5dgt (50/60Hz) |±5%rdg±5dgt (40~400Hz) |
| Ω |
200Ω|±1.5%rdg±5dgt |
| Conductor Size |
Ø40mm max. |
Effect of External Stray Magnetic Field Ø15mm 100A |
10mA AC max. |
| Frequency Response |
40~400Hz |
| Output |
DC200mV against 2000 count |
| Withstand Voltage |
3700V AC for 1 minute |
| Power Source |
6F22(9V) × 1 or AC Adaptor |
| Dimensions |
209(L) × 96(W) × 45(D)mm |
| Weight |
450g approx. |
| Accessories |
7066(Test Leads) 9072(Carrying Case) 8025(Plug for Output Jack) 6F22 × 1 Instruction Manual |
| Optional |
8004/8008(Multi-Tran)* 8022(AC Adaptor)(110V) 8023(AC Adaptor)(220V) 7014(Output Probe) | |
| * These Multi-Trans can not be used for leakage current measurement | | |
| |
|
|
|
|
|
|
|
|
|