Extra wide transformer jaws are best suited for clamping on all three or four wires (3phases) together for leakage current measurement. |
| • |
Frequency filter switch to eliminate the effect of harmonics. |
| • |
Peak hold function. |
| • |
Analogue output terminal. |
|
|
AC A (50/60Hz) |
200mA/2/20/200A/1000A |±1.5%rdg±2dgt (200mA/2/20A) |±2%rdg±2dgt (200A 0~500A) |±5.5%rdg (501~1000A) |
AC A (WIDE) |
200mA/2/20/200/1000A |±1%rdg±2dgt [50/60Hz], |±3%rdg±2dgt [40Hz~1kHz] (200mA/2/20A) |±1.5%rdg±2dgt [50/60Hz], |±3.5%rdg±2dgt [40Hz~1kHz] (200A/0~500A) |±5%rdg [50/60Hz], |±10%rdg [40Hz~1kHz] (501~1000A) |
| Conductor Size |
Ø68mm max. |
Effect of External Stray Magnetic Field Ø15mm 100A |
10mA AC max. |
| Frequency Response |
40Hz~1kHz |
| Output |
AC/DC 200mV against 2000 count |
| Withstand Voltage |
3700V AC for 1 minute |
| Applicable Standard |
IEC61010-1 CAT.III 300V IEC61010-2-032 |
| Power Source |
6F22(9V) × 1 *Continuous measuring time: Approx. 60 hours |
| Dimensions |
250(L) × 130(W) × 50(D)mm |
| Weight |
570g approx. |
| Accessories |
9094(Carrying Case) 6F22 × 1 Instruction Manual |
| Optional |
7073(2WAY Output Cord) | | | |
| |
|
|
|
|
|
|
|
|
|