Frequency Selector Switch to eliminate the effect of harmonics. |
| • |
Three AC current ranges 20mA/200mA/200A. |
| • |
20mA range with a minimum resolution of 0.01mA. |
| • |
Auto power-off function (automatically turns off in about 10 minutes). |
| • |
Rotary switch for easy one finger power-on and range selection. |
|
|
AC A (50/60Hz) |
20/200mA/200A |±3%rdg±5dgt (20/200mA/100A) |±5%rdg±5dgt (200A) |
AC A (WIDE) |
20/200mA/200A |±2%rdg±4dgt [50/60Hz] (20/200mA/0~100A) |±5%rdg±6dgt [40~400Hz] (20/200mA/0~100A) |±5%rdg±4dgt [50/60Hz] (100.1~200A) |
| Conductor Size |
Ø24mm max. |
| Safety Standard |
IEC61010-1 CAT.III 300V IEC61010-2-032 |
Effect of External Stray Magnetic Field Ø15mm 100A |
10mA AC max. |
| Frequency Response |
40~400Hz |
| Withstand Voltage |
3700V AC for 1 minute |
| Power Source |
LR-44(1.5V)× 2 |
| Dimensions |
149(L)× 60(W) × 26(D)mm |
| Weight |
120g approx. |
| Accessories |
9090(Carrying Case) LR-44 × 2 Instruction Manual |
| Optional |
8004/8008(Multi-Tran)* | |
| * These Multi-Trans can not be used for leakage current measurement | | |
| |
|
|
|
|
|
|
|
|
|